Alarm settings

Motor driver

/enableUvloReport (int)motorID (bool)enable

Argument

Argument Range Description
motorID 1-4/1-8, 255 motor ID
enable 0-1 1:Enable, 0:Disable

Executable timing

Always

Description

Set the notification message when UVLO (Undervoltage Lockout) occurs in the specified motor driver. UVLO occurs when the supplied voltage to the motor driver falls below the UVLO turn-off threshold voltage, with or without notification. In this state, the motor cannot be operated. It will be reset when the supply voltage is above the UVLO turn-on threshold.

These thresholds are different between STEP400(PowerSTEP01) and STEP800(L6470). For details, please refer to the corresponding datasheets.

Response

When ULVO occurs same message as /getUlvo will be sent.

Initial value

1 (Enabled)

/getUvlo (int)motorID

Argument

Argument Range Description
motorID 1-4/1-8, 255 Motor ID

Executable timing

Always

Description

Gets the current state of UVLO

Response

/uvlo (int)motorID
Argument Range Description
motorID 1-4/1-8, 255 motor ID
state 0-1 1:UVLO detected 0:No UVLO condition

/enableThermalStatusReport (int)motorID (bool)enable

Argument

Argument Range Description
motorID 1-4/1-8, 255 motor ID
enable 0-1 1:Enable, 0:Disable

Executable timing

Always

Description

Set to send the notification message on change in the temperature status (thermalStatus) of the specified motor driver is detected. On the Bridge shutdown or Device shutdown, the motor state will automatically enters High Z state with of without notification.

Response

When the the thermalStatus changes, the same notification as /getThermalStatus will be sent.

Initial value

1 (Enabled)

/getThermalStatus (int)motorID

Argument

Argument Range Description
motorID 1-4/1-8, 255 Motor ID

Executable timing

Always

Description

Gets the current condition of the ThermalStatus. Thermal status thresholds are different between STEP400(PowerSTEP01) and STEP800(L6470).

Response

/thermalStatus (int)motorID (int)thermalStatus
Argument Range Description
motorID 1-4/1-8, 255 motor ID
thermalStatus 0-3 Thermal status
Thermal status - STEP400
TH_STATUS Thermal status Set condition Release condition
0 Normal - -
1 Warning 135℃ 125℃
2 Bridge shutdown 155℃ 145℃
3 Device shutdown 170℃ 130℃
Thermal status - STEP800
thermalStatus Thermal status Set condition Release condition
0 Normal - -
1 Warning 130℃ 130℃
2 Bridge shutdown 160℃ 130℃

In the Bridge shutdown and Device shutdown states, the motor goes into the High Z state with or without notification.

Initial value

1 (Enabled)

/enableOverCurrentReport (int)motorID (bool)enable

Argument

Argument Range Description
motorID 1-4/1-8, 255 motor ID
enable 0-1 1:Enable, 0:Disable

Executable timing

Always

Description

Set to send a notification when the specified motor driver goes into an overcurrent state (OCD, Over Current Detection). When overcurrent is detected, the device automatically enters High Z state regardless of whether a notification being sent. The threshold can be set with /setOverCurrentThreshold.

Response

On the OCD state, following message will be sent.

/overCurrent (int)motorID
Argument Range Description
motorID 1-4/1-8, 255 motor ID

Initial value

1 (Enabled)

/setOverCurrentThreshold (int)motorID (int)OCD_TH

Argument

Argument Range Description
motorID 1-4/1-8, 255 motor ID
OCD_TH 0-31/0-15 Overcurrent detection threshold
Overcurrent detection threshold - STEP400
OCD_TH Overcurrent detection threshold
0 312.5mA
1 625mA
... ...
30 9.6875A
31 10A
Overcurrent detection threshold - STEP800
OCD_TH Overcurrent detection threshold
0 375mA
1 750mA
... ...
14 5.625A
15 6A

Executable timing

Always

Description

Sets the overcurrent threshold. The setting value range and corresponding currents are different between STEP400(PowerSTEP01) and STEP800(L6470).

Response

You will get the same response as the following /getOverCurrentThreshold to see the actual value.

Initial value

Model Initial value
STEP400 15 (5A)
STEP800 7 (3A)

/getOverCurrentThreshold (int)motorID

Argument

Argument Range Description
motorID 1-4/1-8, 255 motor ID

Executable timing

Always

Description

Get the threshold of overcurrent.

Response

/overCurrentThreshold (int)motorID (float)overCurrentThreshold
Argument Range Description
motorID 1-4/1-8, 255 motor ID
overCurrentThreshold 312.5-10000.0/375.0-6000.0 thresholds in [mA].

Initial value

Model Initial value
STEP400 5000.0 (15)
STEP800 3000.0 (7)

/enableStallReport (int)motorID (bool)enable

Argument

Argument Range Description
motorID 1-4/1-8, 255 motor ID
enable 0-1 1:Enable, 0:Disable

Executable timing

Always

Description

The threshold can be set by /setStallThreshold. When the stall is detected by the specified motor driver, the following message is sent automatically.

Response

/stall (int)motorID
Argument Range Description
motorID 1-4/1-8, 255 motor ID

Initial value

0 (Disabled)

/setStallThreshold (int)motorID (int)STALL_TH

Argument

Argument Range Description
motorID 1-4/1-8, 255 motor ID
STALL_TH 0-31/0-127 Stall detection threshold
Stall detection threshold - STEP400
STALL_TH Stall detection threshold
0 312.5mA
1 625mA
... ...
30 9.6875A
31 10A
Stall detection threshold - STEP800
STALL_TH Stall detection threshold
0 31.25mA
1 62.5mA
... ...
126 3.969A
127 4A

Executable timing

Always

Description

Sets the threshold for stall detection. The setting value range and corresponding currents are different between STEP400(PowerSTEP01) and STEP800(L6470).

Response

You will get the same response as the following /getStallThreshold to see the actual value.

Initial value

Model Initial value
STEP400 31 (10A)
STEP800 127 (4A)

/getStallThreshold (int)motorID

Argument

Argument Range Description
motorID 1-4/1-8, 255 motor ID

Executable timing

Always

Description

Gets the stall detection threshold.

Response

/stallThreshold (int)motorID (float)stallThreshold
Argument Range Description
motorID 1-4/1-8, 255 motor ID
stallThreshold 312.5-10000.0/31.25-4000.0 thresholds in [mA]

Initial value

Model Initial value
STEP400 10000.0 (31)
STEP800 4000.0 (127)

Sensor

/setProhibitMotionOnHomeSw (int)motorID (bool)enable

Argument

Argument Range Description
motorID 1-4/1-8, 255 Motor ID
enable 0-1 1: Prohibit, 0: Allow

Executable timing

Always

Description

Prohibits any motion commands towards the origin point when Home sensor is detected. The direction to the origin point can be configured through the Config Tool or by the /setHomingDirection command.

Initial value

0 (Disabled)

/getProhibitMotionOnHomeSw (int)motorID

Argument

Argument Range Description
motorID 1-4/1-8, 255 Motor ID

Executable timing

Always

Description

Returns whether the motion command towards the origin point is prohibited when Home sensor is detected.

Response

/prohibitMotionOnHomeSw (int)motorID (bool)enable
Argument Range Description
motorID 1-4/1-8 Motor ID
enable 0-1 1:Prohibited, 0:Allowed

/setProhibitMotionOnLimitSw (int)motorID (bool)enable

STEP400 only

Argument

Argument Range Description
motorID 1-4, 255 Motor ID
enable 0-1 1: Prohibit, 0: Allow

Executable timing

Always

Description

Prohibits any motion commands towards the leaving direction from origin point, when the Limit sensor is detected. The direction to the origin point can be configured through the Config Tool or by the /setHomingDirection command.

Initial value

0 (Disabled)

/getProhibitMotionOnLimitSw (int)motorID

STEP400 only

Argument

Argument Range Description
motorID 1-4, 255 Motor ID

Executable timing

Always

Description

Returns whether the motion command towards reverse direction to the origin point is prohibited when Limit sensor is detected.

Response

/prohibitMotionOnLimitSw (int)motorID (bool)enable
Argument Range Description
motorID 1-4 Motor ID
enable 0-1 1:Prohibited, 0:Allowed